Customization: | Available |
---|---|
Phase: | Single Phase |
Type: | On-line |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
er rating | VA/W | 10 KVA/9 KW | 15 KVA/13,5 KW | 20 KVA/18 KW |
Input | Input wiring | Three phase or Single phase with ground (3:1 or 1:1) | ||
Input voltage range | 208VAC-476VAC (three phase) /120VAC-275VAC (signal phase) | |||
Input frequency range | 40-70 Hz | |||
Input power factor | ≥0,99 | |||
Output | Output voltage | 220/230/240 VAC | ||
Output voltage regulation | ±1% | |||
Output wiring | Single phase with ground | |||
Output frequency range | 50/60Hz+/-0.2Hz(battery mode) | |||
Output THDV | <2%(linear load) | |||
<4%(non-linear load) | ||||
Output waveform | Pure sinewave | |||
Crest factor | 3:1 | |||
Overload capability | 10min@105%~125% load;30s@125%~150% load;500ms@>150% load | |||
Efficiency | Line mode | >93,5% | ||
ECO mode | >98% | |||
Battery and charger |
Battery voltage | 192 VDC | 192 VDC/216 VDC/240 VDC optional | |
Battery quantity | 16PCS(External) | default 16PCS(External),16/18/20PCS adjustment | ||
Battery capacity and Backup time |
Depends on customer configuration | |||
Recharge current | 4 A | |||
Parallel | Parallel function | Up to 3 | ||
Display | LCD+LED | load rating/battery capacity/input/output/operating mode/Fault code | ||
Communication and monitoring |
Communication port | RS232 standard offer, USB optional | ||
Extendable communication card |
Dry contact card, USB card, MODBUS card, NMC card are optional | |||
Software | Winpower | |||
Physical parameters |
Product dimension (W*H*D) mm |
212*500*420 | 248*500*565 | |
Product weight (Kg) | 16,9 | 31 | ||
Environment | Operation temperature | 0~40°C | ||
Humidity | 0~95%(non-condensing) | |||
Audible noise | <50dB@1 meter1 | |||
Certification and Standard |
IEC61000,IEC62040,CE |