XTV12800 is a general purpose battery up to12 years in standby service or more than 260 cycles at 100% discharge in cycle service.
XTV has a wider operating temperature range, which makes them more suitable for the systems in harsh condition. As with all CSB batteries, all are rechargeable, highly efficient, leak proof and maintenance free.
Spec
Constant current discharge characteristics:Unit: Amp.(25°C,77°F)
Termination Voltage/ Time
5MIN
10MIN
15MIN
30MIN
60MIN
90MIN
2HR
3HR
5HR
8HR
10HR
20HR
1.60V
35.60
22.00
16.50
9.61
5.51
3.92
3.08
2.13
1.34
0.92
0.77
0.45
1.67V
33.10
21.00
15.90
9.36
5.41
3.85
3.02
2.08
1.31
0.90
0.76
0.44
1.70V
31.90
20.50
15.60
9.24
5.37
3.82
3.00
2.06
1.30
0.89
0.75
0.43
1.75V
29.60
19.60
15.10
9.03
5.30
3.77
2.96
2.02
1.27
0.88
0.74
0.42
1.80V
27.20
18.60
14.40
8.77
5.23
3.71
2.91
1.98
1.25
0.87
0.73
0.42
1.85V
24.50
17.40
13.70
8.44
5.14
3.66
2.87
1.95
1.22
0.86
0.71
0X